Friday, 24 May 2019

Curd Cold Room Specification

Description
MILK COLD ROOM-
1
MILK COLD ROOM-
1 -2
MILK COLD ROOM
-3
Cold Room Dim External in mtr
6.45 mtr x  6.85 mtr x
3.65 mtr ( ht)
6.7  mtr  x  6.85  mtr  x
3.65 mtr ( ht)
6.75 mtr x 6.85 mtr x
3.65 mtr ( ht)
Insulation  for  the  Cold
Room
80 mm thick puf panel for wall & ceiling
80 mm thick puf panel for wall & ceiling
80 mm thick puf panel for wall & ceiling
Insulation of floor
60 mm thick single layer insulation ( PCC
& Kota work by customer)
60 mm thick single layer insulation ( PCC
& Kota work by customer)
60 mm thick single layer insulation ( PCC
& Kota work by customer)
Room Temp
2 deg C to 6 deg C
2 deg C to 6 deg C
2 deg C to 6 deg C
Product to be stored
Liquid MILK
Liquid MILK
Liquid MILK
Storage pattern
Plastic crate
Plastic crate
Plastic crate
Product                     entry temperature
6 deg C 8 deg C
6 deg C 8 deg C
6 deg C 8 deg C
Product entry qty
22000 kg
22000 kg
22000 kg
Total storage capacity
1833 crate
1833 crate
1833 crate
Door Size
78” x 34” x 80 mm
78 x 34” x 80 mm
78” x 34 x 80 mm
No of door
1
1
1
Pull down time
8hr- 10 hr
8hr- 10 hr
8hr- 10 hr
Refrigeration       capacity required
20.5 kw
20.5 kw
20.5 kw
Equipment Offered
11.7 kw x 2 nos = 23.4 kw
11.7 kw x 2 nos = 23.4 kw
11.7 kw x 2 nos = 23.4 kw
Type of Unit
Air cooled
Air cooled
Air cooled
Make     /     Model     of
Condensing unit
Blue Star/ RUAH04012CS-O
Blue Star/ RUAH04012CS-O
Blue Star/ RUAH04012CS-O
Make     /     Model     of
Evaporator unit
Blue Star/ RUAH04012CS-I-N
Blue Star/ RUAH04012CS-I-N
Blue Star/ RUAH04012CS-I-N
Power required
415V/ 3 phase/ 50 Hz
415V/ 3 phase/ 50 Hz
415V/ 3 phase/ 50 Hz
Power   consumption   of each unit
5.5 kw x 2 nos = 11 kw
5.5 kw x 2 nos = 11 kw
5.5 kw x 2 nos = 11 kw