Friday, 21 June 2019

AC Drives


AC Drives


1. AC Drives is fully engineered panels
with necessary switchgear.

2. Panel shall be having three phase indications, Voltmeter & Selector Switches.

3. Supply Voltage for control supply shall be 110VAC. Start/Stop switches push
Buttons, indications, shall be provided for each drive panel.

4. Bus Bar/ Power Cable shall be High conductivity and suitable rated as per drive
requirement. Color Sleeves shall be provided for each panel.

5. Supply, lying routing of field Cable & Wiring accessories shall be not in our scope.


TECHNICAL DATA
Make
SIEMENS

Input Voltage
380V to 480 V 3AC ±10%

Input frequency
47Hz to 63Hz

Output frequency
0Hz to 650Hz (in V/f mode)

Power factor
≥0.95

Inverter efficiency
96% to 97%

Control Method
Linear V/f; quadratic V/f characteristic; multipoint characteristic
(programmable V/f characteristic); flux current control (FCC)
Digital Inputs 6 fully programmable isolated digital inputs; switchable PNP/NPN

Analog Inputs 2 programmable analog inputs

Digital Outputs 3 programmable outputs

Analog Outputs 2 programmable outputs

Protection level IP-20

Protection features for
Under-voltage, over-voltage, overload, earth faults, short
circuits, stall prevention, locked motor, motor over temperature,
inverter over-temperature, parameter PIN protection

TECHNICAL FEATURES
Microprocessor based operation for all closed loop and open loop functions.
PWM Technology for generation of variable voltage variable frequency supply
for motor.
Voltage source DC link converter
IGBT based inverter section resulting in higher efficiency low losses
Slip-compensation facility
Current limiting control
Voltage boost
Flexible control functions
Max./Min. frequency set points
Ramp smoothing
Stall protection
Auto Restart


No comments: