BILL OF QUANTITIES
|
||||
SR.NO.
|
DESCRIPTION
|
UNIT
|
QTY
|
|
|
|
|
|
|
1.2
|
DOUBLE
SKIN AIR HANDLING UNITS
|
|
|
|
a
|
Double
skin air handling units fabricated from outer skin with 0.63 mm thick
precoated G.I sheet & plain 0.63 mm thick inner G.I sheet with 25 mm
thick injected puf insulation with Aluminum extruded frame work having Thermal
break profile.
|
|
|
|
b
|
Mixing
Chamber
|
|
|
|
c
|
Pre
Filter Section
|
|
|
|
d
|
Cooling Coil Section with 4 rows deep cooling
coil h made of copper tubes and aluminium fins.
|
|
|
|
e
|
Fan
section complete with backward curved multi-louvered centrifugal blower
suitable for various CFM working against a static pressure of 110 mm. ( SPARK PROOF)
|
|
|
|
f
|
Crompton/Equivalent
make TEFC squirrel cage induction Flame Proof motor suitable for
operation on AC 3 Phase, 415 volts, 50 c/s. supply
|
|
|
|
g
|
V belts pulleys and guards
|
|
|
|
h
|
MICROVEE FILTERS section
|
|
|
|
i
|
Hepa Filters section
|
|
|
|
|
|
|
|
|
1.2.1
|
AHU 1 /
8590 CFM / 110 MM S.P / 7.5 H.P / 4P
|
No.
|
1
|
|
1.2.2
|
AHU 2 /
4900 CFM / 110 MM S.P / 7.5 H.P / 4P
|
No.
|
1
|
|
1.2.3
|
AHU 4 /
5900 CFM / 110 MM S.P / 3 H.P / 2P
|
No.
|
1
|
|
|
|
|
|
|
1.2
|
DOUBLE
SKIN AIR HANDLING UNITS
|
|
|
|
a
|
Double
skin air handling units fabricated from outer skin with 0.63 mm thick
precoated G.I sheet & plain 0.63 mm thick inner G.I sheet with 25 mm
thick injected puf insulation with Aluminum extruded frame work having Thermal
break profile.
|
|
|
|
b
|
Mixing Chamber
|
|
|
|
c
|
Pre
Filter Section
|
|
|
|
d
|
Cooling Coil Section with 4 rows deep cooling
coil h made of copper tubes and aluminium fins.
|
|
|
|
e
|
Fan
section complete with backward curved multi-louvered centrifugal blower
suitable for various CFM working against a static pressure of 110 mm. ( SPARK PROOF)
|
|
|
|
f
|
Crompton/Equivalent
make TEFC squirrel cage induction Flame Proof motor suitable for
operation on AC 3 Phase, 415 volts, 50 c/s. supply
|
|
|
|
g
|
V belts pulleys and guards
|
|
|
|
h
|
MICROVEE FILTERS section
|
|
|
|
|
|
|
|
|
1.2.1
|
AHU 3 /
2530 CFM / 110 MM S.P / 7.5 H.P / 4P
|
No.
|
1
|
|
|
|
|
|
|
2
|
FORCED
DRAFT VENTILATION SYSTEMS:
|
|
|
|
1.1
|
Supply Air Washer
|
|
|
|
|
Single skin supply air washer unit fabricated
from 1.6 mm thick G.I. Sheet
complete with following Sections for ventilation systems. Fan Section with forward curve fan & Motor
Pre filter Section with 10 Microns Pre-filters. 5 Micron Filter section
|
|
|
|
|
Filter
Section complete with pre-filters designed to remove particles down to 10
Microns with an efficiency of 90% on ASHRAE STD. 52-56 and 90% on BS 2831
Test Dust No. 2 (Junior Filter) in M.S. construction.
|
|
|
|
|
Celldeck Pad, water circulation system with pump
and float valve,V-Belt & Pulley,GI volume control damper
|
|
|
|
|
Kruger
make Fan section complete with forward curved multi-louvered centrifugal
blower suitable for working against a static pressure of 50 mm
|
|
|
|
2.1.1
|
AW-1 /
8500 CFM / 50 MMSP / 3 HP / 4P
|
Nos
|
1
|
|
2.1.2
|
AW-2 /
9000 CFM / 50 MMSP / 2 HP / 4P
|
Nos
|
1
|
|
|
|
|
|
|
3
|
EXHAUST FDV
|
|
|
|
a
|
Single
skin exhaust air handling unit fabricated from 1.6 mm thick G.I. Sheet
complete with following Sections for ventilation systems. Fan Section with
forward curve fan & Motor,Pre filter Section with 10 Microns Pre –
filters.
|
|
|
|
b
|
Mixing
Chamber
|
|
|
|
c
|
Filter Section complete with pre-filters designed
to remove particles down to 10 Microns with an efficiency of 90% on ASHRAE
STD. 52-56 and 90% on BS 2831 Test Dust No. 2 (Junior Filter) in M.S.
construction.
|
|
|
|
d
|
Kruger
make Fan section complete with forward curved multi-louvered blower suitable
for working against a static pressure of
25 mm as under.
|
|
|
|
e
|
Crompton/Equivalent
make Flame Proof squirrel cage induction motor suitable for operation on AC 3
Phase, 415 volts, 50 c/s. supply
|
|
|
|
f
|
V belts pulleys and guards
|
|
|
|
3.1.1
|
EFDV-1
/ 8500 CFM / 50 MMSP / 3 HP / 4P
|
Nos
|
1
|
|
3.1.2
|
EFDV-2
/ 9000 CFM / 50 MMSP / 2 HP / 4P
|
Nos
|
1
|
|
|
|
|
|
|
3.0
|
AIR
DISTRIBUTION SYSTEM
|
|
|
|
|
DUCTING
|
|
|
|
3.1
|
Sheet metal work comprising of G.I. ducting
with RTV sealant,sizes & quantities are as under:
|
|
|
|
3.1.1
|
24 G
|
sq.ft
|
12000
|
|
3.1.2
|
22 G
|
sq.ft
|
3000
|
|
3.2
|
INSULATION
|
|
|
|
3.2.1
|
Supply
air ducts wll be insulated with 19 mm thick factory laminated A/L foil
covered polythene form
|
Sq.ft
|
4700
|
|
3.2.2
|
Return
air ducts wll be insulated with 9 mm thick factory laminated A/L foil
covered polythene form
|
Sq. ft
|
4700
|
|
|
|
|
|
|
3.3
|
Factory
fabricated 18G G.I.risers for return air
|
Sq.ft
|
1300
|
|
3.4
|
Return air riser grilles with front operated volume control damper
with filter.The front cover will be easily detachable .
|
Sq.ft
|
60
|
|
3.6
|
Supply
Air Grill with V.C.D in Extruded
aluminium construction
|
Sq.ft
|
115
|
|
3.7
|
Return
Air Grill with V.C.D in Extruded
aluminium construction
|
Sq.ft
|
55
|
|
3.8
|
GI
volume control damper
|
Sq.ft
|
60
|
|
|
|
|
|
|
4.3
|
Hepa
Filter for AHU
|
|
|
|
|
HEPA FILTERS
(High efficiency particulate air) designed to remove particles down to
0.3 Microns from air streams with an efficiency of 99.97%. The filter matrix comprises specially
treated glass fiber media with machine pleated aluminium separators. I
|
|
|
|
4.3.1
|
610 x 610 x 150
|
Nos
|
12
|
|
|
610 x 610 x 305
|
Nos
|
17
|
|
|
|
|
|
|
4.3.2
|
Terminal Hepa Filter for class 10000
|
|
|
|
|
HEPA FILTERS
(High efficiency particulate air) designed to remove particles down to
0.3 Microns from air streams with an efficiency of 99.97%. The filter matrix comprises specially
treated glass fiber media with machine pleated aluminium separators. I
|
|
|
|
4.3.2.1
|
610 x 610 x 150
|
Nos
|
3
|
|
|
|
|
|
|
4.3.3
|
Terminal
Hepa Filter Box
|
|
|
|
|
HEPA
Filters will be housed in a HEPA housing fabricated out of 16G CRCA sheet
duly powder coated. A protective
screen fabricated out of 16G aluminium sheet duly powder coated with 70% open
area will also be provided alongwith HEPA box.
|
|
|
|
4.3.3.1
|
610 x 610 x 150
|
Nos
|
15
|
|
|
610 x 610 x 305
|
Nos
|
17
|
|
|
|
|
|
|
6.1
|
Chilled water loop piping including suitable size of 3way mixing
valve,Balancing valve,Isolation valve(5 nos butterfly valves) 2 nos
Temperature gauges,2 Nos Pressure gaugeswith companion flanges to be
connected to utility pipe.
|
|
|
|
6.1.1
|
AHU-1-18.95 tr
|
Set
|
1
|
|
6.1.2
|
AHU-2- 11.2 tr
|
Set
|
1
|
|
6.1.3
|
AHU-3- 5.75 tr
|
Set
|
1
|
|
6.1.4
|
AHU-4-12.3 tr
|
Set
|
1
|
|
|
|
|
|
|
6.20
|
Humidistat
-FLP
|
Nos
|
4
|
|
6.3
|
Airstat-
FLP
|
Nos
|
4
|
|
|
|
|
|
|
7
|
ELECTRICAL
WORKS
|
|
|
|
7.1
|
Electrical
Panel
|
|
|
|
|
Design,
supply, installation, testing & commissioning of one Electrical panel for
all System as per air flow diagram. The Panel should consist of Incomer MCB,
Contactors, Upto 5HP DOL rating and
above shall be Delta starters, Relays, Push button (On / Off / Reset),
Indicating Lam
|
|
|
|
7.1.1
|
Panel -
1
|
Nos
|
1
|
|
7.1.2
|
Panel -
2
|
Nos
|
1
|
|
|
|
|
|
|
7.6
|
Electric
strip Heater (flame proof )
|
|
|
|
|
Strip
heaters in suitable banks will be provided for various systems for Monsoon
Reheating.
|
|
|
|
7.6.4
|
1.0 KW
(flame proof)
|
Nos
|
9
|
|
7.6.5
|
2.0
KW( flame proof)
|
Nos
|
3
|
|
7.6.6
|
3
KW( flame proof)
|
Nos
|
3
|
|
|
|
|
|
|
7.6.2
|
Electric
Heater Plenum fabricated out of 20G G.I. Sheets in single skin
construction. Door will be double
skin type with PUF injected
|
Nos
|
4
|
|
|
|
|
|
|
8
|
MAGNEHALIC GAUGES with Magnehalic Guage
Boxes in M.S Epoxy painted with S.S front cover for measuring room pressure
difference across the room and AHU filter.
|
Nos
|
8
|
|
|
|
|
|
|
9
|
Testing,
Commissioning, Validation and Documentation Charges
|
Set
|
1
|
|
|
Consisting
of
|
|
|
|
|
Air
Balancing Test
|
|
|
|
|
Temperature
and RH Testing
|
|
|
|
|
Pressure
Differential Setting
|
|
|
|
|
Particle
Counting
|
|
|
|
|
DOP
Testing
|
|
|
|
|
DQ,IQ.OQ
& PQ Protocols
|
|
|