|
DEHUMIDIFIER.
Just for the interest of non-technical users, we will provide the rule of thumb sizing for those who are
interested mainly in the small portable units.
a) A 12 L/day unit is able to keep a 150 sq ft x 8 ft ( 14 sq meter x 2.4 m ) space at 55% RH.
b) A 16 L/day unit is able to keep a 200 sq ft x 8 ft ( 19 sq meter x 2.4 m ) space at 55% RH.
55% RH is a general minimum requirement for most low level storage. For lower RH level like 45-50%
RH control, reduce the space by 30-35% by floor area. If one unit is too small, go for 2 units, or use the 30-45 L/day
( Note: the above sizing is based on an unventilated room. Room with central air-conditioning or exhaust is generally
difficult to estimate as the volume of Ventilation Air creates a very high humidity load.
Just for the interest of non-technical users, we will provide the rule of thumb sizing for those who are
interested mainly in the small portable units.
a) A 12 L/day unit is able to keep a 150 sq ft x 8 ft ( 14 sq meter x 2.4 m ) space at 55% RH.
b) A 16 L/day unit is able to keep a 200 sq ft x 8 ft ( 19 sq meter x 2.4 m ) space at 55% RH.
55% RH is a general minimum requirement for most low level storage. For lower RH level like 45-50%
RH control, reduce the space by 30-35% by floor area. If one unit is too small, go for 2 units, or use the 30-45 L/day
( Note: the above sizing is based on an unventilated room. Room with central air-conditioning or exhaust is generally
difficult to estimate as the volume of Ventilation Air creates a very high humidity load.
2) CALCULATING HUMIDITY LOAD BY ENGINEERING
METHOD
For a more ACCURATE selection, we have the following:
In this exercise, we have included the 3 biggest factors that contribute to the humidity load. There are a lot
more other factors that contribute to the moisture load but they may need some expertise to understand and
calculate. A more stringent formula is needed for low humidity application below 40% RH or low temperature
( below 15 deg C ). This is done only by trained engineers. Total load will be sum of all the 3 following factors.
For a more ACCURATE selection, we have the following:
In this exercise, we have included the 3 biggest factors that contribute to the humidity load. There are a lot
more other factors that contribute to the moisture load but they may need some expertise to understand and
calculate. A more stringent formula is needed for low humidity application below 40% RH or low temperature
( below 15 deg C ). This is done only by trained engineers. Total load will be sum of all the 3 following factors.
There are 3 main factors are :
1) INFILTRATION is the average air that can come in
thro' the walls and cracks. It is directly proportional to the difference
between the indoor and outdoor Humidity, and the size of the space. Stringently, it is proportional to the areas of the 4 walls
plus ceiling and floor. But to simplify the formula, total space volume is used instead, with a additional K-factor in the attached tables .
between the indoor and outdoor Humidity, and the size of the space. Stringently, it is proportional to the areas of the 4 walls
plus ceiling and floor. But to simplify the formula, total space volume is used instead, with a additional K-factor in the attached tables .
INFILTRATION
LOAD (L/hour) = (H out - H in ) x 0.0012 x Space Volume x K-factor
|
H out
is the Absolute Humidity in g/kg of the surrounding or out door air.
H in is the Absolute Humidity in g/kg of the space to be dried.
0.0012 is the density of air.
Space Volume is the volume of the space, height x width x length in cubit meter.
K-factor is the factor that converts the volume into surface area of exposure.
H in is the Absolute Humidity in g/kg of the space to be dried.
0.0012 is the density of air.
Space Volume is the volume of the space, height x width x length in cubit meter.
K-factor is the factor that converts the volume into surface area of exposure.
K-factor table
SPACE LESS THAN
|
K-Factor
|
80 CUBIT METER
|
0,5
|
200 CUBIT METER
|
0,4
|
400 CUBIT METER
|
0,35
|
600 CUBIT METER
|
0,3
|
1000 CUBIT METER
|
0,27
|
2000 CUBIT METER
|
0,23
|
3000 CUBIT METER
|
0,21
|
4000 CUBIT METER
|
0,19
|
5000 CUBIT METER
|
0,18
|
eg : A space of 20 x 10 x 10
meter space. Out door 30 deg C 70% RH. Required condition is 23 deg C 50% RH.
Calculate the infiltration load.
Calculate the infiltration load.
The first step is to convert the
condition to absolute humidity in g/kg.
Out door 30 deg C 70% RH = 18.5 g/kg (Absolute Humidity)
Space 23 deg C 50% RH = 8.6 g/kg (Absolute Humidity)
Out door 30 deg C 70% RH = 18.5 g/kg (Absolute Humidity)
Space 23 deg C 50% RH = 8.6 g/kg (Absolute Humidity)
P-factor : is a basic offset for differential value between
the H out and H in. The higher the differential,
the greater the P-factor. It is found that the greater the difference between H out and H in, the greater
the vapour pressure has its effect in pushing the moisture through a wall. It is added into the formula
to improve the offset in the form of a mathematical division.
the greater the P-factor. It is found that the greater the difference between H out and H in, the greater
the vapour pressure has its effect in pushing the moisture through a wall. It is added into the formula
to improve the offset in the form of a mathematical division.
P-factor = (H out - H in )
/ 11.5
INFILTRATION =
(H out - H in )
x 0.0012 x Space Volume x K-factor x P-factor
INFILTRATION = ( 18.5-8.6 ) x 0.0012 x 2000 x 0.23 x 0.86 = 4.7 L/hr
ie there is 4.7 Litre of water getting into the space every hour.
INFILTRATION = ( 18.5-8.6 ) x 0.0012 x 2000 x 0.23 x 0.86 = 4.7 L/hr
ie there is 4.7 Litre of water getting into the space every hour.
2) HUMAN LOAD - This is a simple load based on estimation
of human activities and H-factor
( human activity level )
( human activity level )
HUMAN LOAD ( L/hr ) = Number of
people x H-factor x 0.065
|
H-Factor Table
PASSIVE, OFFICE WORK
|
2,0
|
SOME MEASURE OF MOVEMENT
|
2.5
|
HEAVY LABOUR / EXERCISE
|
3,0
|
3) VENTILATION - This is the estimate of the exhaust
air or fresh air volume entering the room. Fresh air is needed for
human being. Each person requires an estimate of 20 CMH of fresh air. Door opening is another cause for ventilation.
Every time the door opens it adds to the fresh air intake and should be part of this formula.
human being. Each person requires an estimate of 20 CMH of fresh air. Door opening is another cause for ventilation.
Every time the door opens it adds to the fresh air intake and should be part of this formula.
VENTILATION LOAD ( L/hr)= AIR INTAKE
(CMH) x (H out - H in ) x 0.0012
|
where H out
- H in are similarly defined as in
INFILTRATION LOAD.
DOOR OPENING LOAD / DOOR LOAD
Door opening can be considered as part of the Ventilation Load as it introduces air into the room each time a door is
opened. It is measured as the added quantity of AIR INTAKE (CMH) in Ventilation Load.
Door opening can be considered as part of the Ventilation Load as it introduces air into the room each time a door is
opened. It is measured as the added quantity of AIR INTAKE (CMH) in Ventilation Load.
DOOR LOAD (CMH) = AREA OF DOOR (sq.
meter ) x 3 x time(sec) door stayed opened x No. of
openings/Hr
|
eg. A 5 sq.meter door opens 2 times
per hour, each time stayed opened for 6 seconds is equal to =
5 x 3 x 6 x 2 = 180 CMH ventilation air.
Note: The initial condition of the
untreated space is usually just a good indication of the "wetness
level" and is NOT part
of the Moisture Load calculation Formula.
of the Moisture Load calculation Formula.
Most of the Dehumidifiers catalog have some values indicated like 16L/day or 12 L/day. This values are
indicative of the capacity of the dehumidifiers. Because different manufacturers use a different condition
to measure this value, there is always confusion in selection.
For example: Unit "A" with
15 L/day at 85% RH 33 deg C may be smaller in capacity than unit "B"
which
states a 12 L/day capacity at 70% RH26 deg C. You may ask ," That's confusing ! " Yes, it is !
states a 12 L/day capacity at 70% RH26 deg C. You may ask ," That's confusing ! " Yes, it is !
The reason is that the Dehumidifiers
have different capacity at different temperature and humidity.
To simplify the description, a specified condition like 80% RH 30 deg C is the standard reference for most brands.
To simplify the description, a specified condition like 80% RH 30 deg C is the standard reference for most brands.
However, the better systems usually
have another reference point like 27 deg C 60% RH or 55% RH 25 deg C
etc intermediate value as mid point reference. This middle values are the real functioning range of the Dehumidifier
/ DH as we usually want to keep the room at lower RH than 80%. Some industrial system come with a performance
curve chart.
etc intermediate value as mid point reference. This middle values are the real functioning range of the Dehumidifier
/ DH as we usually want to keep the room at lower RH than 80%. Some industrial system come with a performance
curve chart.
No comments:
Post a Comment