Tuesday, 11 June 2019

Cooling Tower 125CMPH Specification


Cooling Tower 125m3/hr. Specification

TYPE
Induced draft cross flow
CAPACITY
CMH
125
NO. OF CELL

One
CAPACITY PER CELL
CMH
125
HOT WATER TEMPERATURE
DEG C
41
COLD WATER TEMPERATURE
DEG C
32
WET BULB TEMPERATURE
DEG C
28
RANGE
DEG C
9
APPROACH
DEG C
4
EVAPRORATION LOSS


DRIFT LOSS MAXIMUM


INLET PRESSURE


HEAT DISSIPATION


RELATIVE HUMEDITY


DESIGN WIND PRESSURE
150 Kg/M2 (160KmpH)

TOATL OPERATING WEIGHT
14210 Lbs

TOTAL WETED SURFACE AREA


DIMENSIONS


MODEL NO.
TOWER DIMESION(L X W X H)
FEET
23'-2" x 8'-7 1/2" x 12'-4 1/8"
FAN DIMESION (DIA & NO OF BLADE)
Dia, No.
72", 06,
NO. OF FAN
NO.
One
CAPAICITY OF FAN


FAN SPEED
 (RPM)
535
MOTOR
HP, RPM, enclosure, V/Ph/Hz
10, 1500 TEFC/WP 415/3/50
NO. OF MOTOR
NO.
1
FAN POWER CONSUMPTION
(BHP)
7
GEAR BOX


PUMPING HEAD


MATERIALS OF CONSTRUCTION


FRAME WORK
ASCU TREATED TIMBER
FILL
PVC V BAR
ELIMINATORS BLADE
ASCU TREATED TIMBER /PVC
FILL SUPPORT GRID
SS 304
CASING & LOUVERS
CORRUGATED ACB
HOT WATER BASIN


ELIMINATOR FRAME
Herringbone pattern, treated wood
BOLT,NUTS
MS HDG
NAILS
SS 304
BASIN
RCC
MECHANICAL EQUIPMENT SUPPORT
Galvanized Steel