AHU - 5000 CFM
Specification
Unit Make: Kleanair
Outer Skin : 0.6mm
Pre Coated G.I
Inner: 0.6mm
Plain GI
Frame Work: Hollow
Extruded Aluminium Profile
Thickness of Insulated Panels: 25mm Thick CFC Free PUFF
Material of Drain Pan: 20
G (SS-304)
Drain Pan Insulation: 9mm Thick
Coil casing : GI
Chilled Water Cooling Coil: 1/2'' / 6Row Deep
Header : M.S
Material of Tube : Copper
Testing Pressure: 21kg/cm2
Tube Dia: 12.7mm
Thickness of Tube : . 41mm
Fin Spacing : 12-13
FPI
Material of Fins : Aluminium
Thickness of Fins : 0.15mm
Media of Filters: Non
Woven Synthetic
Filter @ 500FPM : Pre. And fine filter
Canvass Connection: Fire
Retardant
Driver Set: Taper
Lock Driver with V-Belt
Motor Type: Three
Phase, 50HZ Squirrel Cage Induction TEFC AC
Type:
FM
Air Qty (CFM): 5000
S.P (MM WG):
50
Row Deep: 6 Row
Cooling Area (Sq. Ft.): 10
Pre and fine filter @ 500FPM:
Fan Dia: KAT-18/18
Velocity: 8.87
RPM: 865
Motor Kw: 3.7
2. G.S.S Ducting fabricated out of
24G/22 G G.I Sheets including supports, suspenders, nut bolts etc. Providing Duct insulation with 9
mm thick closed cell cross link EXPE with aluminium foil ( supreme make) to
duct with adhesive.
MS/GI Powder
coated Double deflection grille with VCD.
GI Duct
damper fabricated out of 20 gauge blade and 20 gauge frame duly Aluminum enamel
painted.
Electrical Panel with starter MCB (RYB), voltmeter &
Ammeter, Power supply for 3 way valve. Cabling, earthing, cable tray for AHU
Air flow switch with its installation in duct
Pipe with Insulation for chilled water
valves with insulation of Butterfly valve - 02 nos, Y strainer, Balancing valve, 3 way
valve.
Auto Air Vent with valve