Cooling Tower Specification
Type : INDUCED DRAFT SQUARE COUNTER FLOW
Quantity / Number of Cells : 1 No.
Tower Size (LxWxH) : 3050 mm x 3050 mm x 3200 mm - PER
CELL
FRP BASIN Size (LxWxH) : 3050 mm x 3050 mm x 250 mm - PER
CELL
Shipping / Operating Weight : 1000
Kgs. / 3000 Kgs. - PER CELL
DESIGN
PARAMETERS PER CELL
Water Flow Rate : 182 m3/hr
Inlet (HWT) : 37 °C
Outlet (CWT) : 32 °C
Delta T : 5 °C
Design Wet Bulb Temperature : 28 °C
Cooling Capacity : 9,10,000 Kcal/hr
Total Wetted Surface Area : 2034 m2
AUXILIARY
EQUIPMENT PER CELL
Type of Fan : Axial Flow, DIRECT
DRIVEN
Air Quantity / Fan : 24.2 m3/sec
Fan Diameter / Speed : 1800 mm / 720 RPM
Absorbed
BKW at Fan Shaft : 5.9 kW
Electric
Motor Rating : 7.5 kW / 10 HP / 750 RPM
Vertical Flange Mounted, Squirrel
Cage
Weather Proof Induction Motor
suitable for supply of 415 V ± 6% 50
Hz ± 3%
with class of insulation “F” and
IP-55 Degree of
Protection.
WATER
LOSSES PER CELL
Evaporation Loss : 0.81 % of Circulating Water.
Drift Loss (Max.) : 0.005 % of Circulating Water.
Blow Down : 0.20 % of Circulating
Water.
Make-up Water Quantity : 1.015 % of Circulating Water.
MATERIAL OF
CONSTRUCTION
Casing / Basin : Seamless FRP (Panel Type)
Fills : PVC Honey Comb type Fills
Drift Eliminators : PVC
Nozzles : PP/ABS LOW PRESSURE DROP
NON CLOGGING TYPE
Water Distribution Headers : PP WITH FRP MOULDED. NON COROSSIVE
Fan Blades / Hub : FRP
Resting : MS HDG
PVC Fills Support/ Eliminators
Support : FRP Pultruded
Fan-Motor mounting frame : MS-HDG
No comments: