Thursday, 6 June 2019

Refrigeration Load & Chilled Water Requirement

Refrigeration Load & Chilled Water Requirement
Sr. No.
Equipment's Name
Capacity (ltr. /hr)
Delta t
Heat Load (Kcal)
Chilled Water Delta t
Chilled Water Requiment
Refrigeration Pick Load in TR
1
Milk Chiller - 1 (8°C to 4°C)
20000
4
80000
2
40000
26.67
2
Milk Chiller - 2 (8°C to 4°C)
20000
4
80000
2
40000
26.67
3
Milk Pasteurizer 1 (80°C to 4°C) regeneration 90%
20000
8
160000
2
80000
53.33
4
Milk Pasteurizer 2 (80°C to 4°C) regeneration 90%
20000
8
160000
2
80000
53.33
5
Milk Pasteurizer 3 (80°C to 4°C) regeneration 90%
5000
8
40000
2
20000
13.33
6
Cream Pasteurizer - 1 (90° to 8°C) 80% regeneration
3000
16
48000
2
2400
16.00
7
Cream Pasteurizer - 2 (90° to 8°C) 80% regeneration
3000
16
48000
2
2400
16.00
8
Cream Ageing Tank - 1 (10 deg to 12 deg)
3500
2
7000
2
3500
2.33
9
Cream Ageing Tank - 2 (10 deg to 12 deg)
3500
2
7000
2
3500
2.33
10
Cream Ageing Tank - 3 (10 deg to 12 deg)
3500
2
7000
2
3500
2.33
11
Dehumifier (in SMP Plant) (8°C to 1°C)
30000
7
210000
7
30000
70.00
12
Butter Milk Chiller (15 deg. to 4deg.C)
5000
11
55000
3
18333
18.33
13
Concentrate Packing (10 deg. To 1deg.)
5361
10
53610
2
26805
17.87

Total
141861

902000

323633
318.54